What is the difference between VAV and FCU?

Published: August 18, 2022

The VFD will try to maintain the speed (RPM) of the fan so that the static pressure in the duct at the location of the static pressure sensor maintains some minimum set-point, such as 1.25” sp. The static pressure sensor sends a signal to the VFD and the speed of the fan is adjusted according to the set-point required. HRV is invented by Daikin Air Conditioning in 1992, it is now called the Total Heat Exchanger. This type of air conditioner recovers lost heat energy through ventilation equipment, reducing the load on the air conditioner while maintaining a comfortable and fresh environment. In addition, HRV can be used in conjunction with VRV systems, commercial split systems and other air conditioning systems, and can automatically switch ventilation modes to further improve energy-saving effects.

The minimum CFM setpoint can be somewhere between 30% and 50% of the maximum cooling setpoint. Minimums are set by some code jurisdiction so that the minimum ventilation rate is always achieved. In California see Title-24 Sec 120.1 Requirements for Ventilation and Indoor Air Quality. This primary supply air will also bring a percentage of mandatory ventilation air (Outside Air).

  1. A typical system is usually comprised of a large air handler, central ductwork system, and a relatively large equipment room.
  2. The static pressure setting in the main supply duct is reduced to a point where one VAV box damper is nearly full open.
  3. This type of air conditioner recovers lost heat energy through ventilation equipment, reducing the load on the air conditioner while maintaining a comfortable and fresh environment.
  4. As you can see in the diagram above the VAV Damper goes from a minimum of 30% open, whatever the minimum required to meet ASHRAE 62, all the way to the damper being 100% open.
  5. The fan filter unit is a terminal purification equipment that combines a fan and a filter (high-efficiency filter (HEPA) or ultra-high-efficiency filter (ULPA)) to form its own power.
  6. Noise output from FCUs, like any other form of air conditioning, depends on the design of the unit and the building materials surrounding it.

At present, air handling units mainly have several forms such as ceiling type, vertical type, horizontal type and combined type. Among them, the ceiling-type air handling unit is also called a hanging cabinet; the combined air handling unit is also called a combined air cabinet. A DOAS terminal is a fan-powered air terminal mounted in the ceiling plenum, with a chilled water cooling coil mounted at the inlet from the ceiling plenum. Heating coils (hot water or electric) are included in DOAS terminals which serve spaces requiring heat. Due to their simplicity, flexibility and easy maintenance, fan coil units can be more economical to install than ducted 100% fresh air systems (VAV) or central heating systems with air handling units or chilled beams. FCUs come in various configurations, including horizontal (ceiling-mounted) and vertical (floor-mounted) and can be used in a wide range of applications from small residential units to large commercial and industrial buildings.

#1 Constant Static Pressure Control Method

Using a DDC control system with VAV boxes that have a flow station and temperature sensor at the supply air discharge the system can determine the amount of reheat. The use of this strategy is required by Title-24 (California) and ASHRAE 90.1 for system that have DDC to the zone level. The static pressure setting in the main supply duct is reduced to a point where one VAV box damper is nearly full open. This would require that the VAV box actuators can report their damper position, best performed with an analog output. The pressure sensor in the duct will send a signal to the Variable Frequency Drive (VFD) causing the supply and return fans to slow down or reduce its RPM. If the pressure in the duct decreases because the VAV boxes are opening due to the need for additional cooling, the pressure sensor will send a signal to increase the fan speed (RPM).

Heating Mode

I suspected before that higher fan power of VAV results in more temperature increase through fan and hence more space cooling requirement. But after manually change the delta T through fan, the effect is not very obvious that the space cooling increase proportion drops from 32% to around 28%.seems it is not the main cause. Lately I am modelling an office & hotel complex through eQUEST with energy conservative strategies added one by one to test the energy saving effect.

Unit ventilator

Fan coil units are an excellent delivery mechanism for hydronic chiller boiler systems in large residential and light commercial applications. In these applications the fan coil units are mounted in bathroom ceilings and can be used to provide unlimited comfort zones – with the ability to turn off unused areas of the structure to save energy. The fan motors within a fan coil unit are responsible for regulating the desired heating and cooling output of the unit. Some utilize an AC transformer, adjusting the taps to modulate the power supplied to the fan motor.

Fan coil systems are comprised of water-to-air coil air handlers connected via a two or four-pipe insulated water loop. Fan coils require complex chillers and boilers to provide water loop fluid in a particular temperature range (i.e., chilled water for cooling and hot water for heating). Two-pipe fan coils have a major disadvantage as control is substantially limited to whatever mode the system is currently set at (i.e., cooling or heating). A four-pipe version can be installed that requires both chilled and heated water to be available at the same time.

Usually, there are either 2 or 4 pipes made of ABS, steel or copper that go through the floor. Functionally, according to the requirements of the use environment, it can achieve constant temperature and humidity or simply provide fresh air. After dust removal, dehumidification (or humidification), cooling (or heating) and other treatments, it is sent to the room through the fan, and the original air in the room is replaced when it enters the indoor space. Of course, the functions mentioned above must be determined according to the needs of the use environment.

• VAV systems are very cost effective from a chilled-water and heating-water-pumping perspective. Because the unit transfers heat to the space using forced convection, the coil heat transfer area required is reduced as compared to a chilled beam. The reduction in coil heat transfer surface area results in lower coil water side pressure drop and lower pumping energy. Forced convection heat transfer also yields higher water side delta T which also results in lower pumping energy.

The point-of-sale tools are downloadable documents to help aid you in conversations with customers making decisions about heating and cooling systems. There are many types of specialized HVAC technology used in commercial buildings and these are often much different from those terms used in common residential applications. We thought it would be helpful to provide a summary list of the various types of commercial air conditioning systems used in the US today. Reviewing this list prior to or during conversations with your HVAC contractor might allow you to be more informed and less confused about the solutions being proposed for your commercial air conditioning needs. Before we get any deeper into this subject we need to cover the basics of zoning.

The circulating air conditioning box is also called the indoor air circulation unit, which mainly sucks and discharges indoor air to ensure indoor air circulation. The outdoor unit is for air-cooled heat exchange, and the indoor units adopt the direct evaporative heat exchange. Fan coil units (FCU’s) are small single units that condition air and move it to the space via minimal ductwork. They can be used to manage small loads [KW], usually located in single rooms, recirculating the air. VAVs are like automated volume damper which is installed to regulate the flow of air in conditioned space according to the thermostat setting.

Multiple-zone systems

A concealed fan coil unit will typically be installed within an accessible ceiling void or services zone. It is quite common for the return air not to be ducted and to use the ceiling void as a return air plenum. On the other hand, because the central air handling unit provides all cooling to the spaces, it is required to move a much greater volume of air. Thus, the floor space required for air handling equipment and vertical duct risers (shafts) is much more significant when compared to the other systems. The heating hot water valve will modulate open providing a range of heating hot water flow (GPM) to meet the heating load.

• VAV system generally have lower maintenance requirements as compared to the other systems. This is because there is no chilled water coil at the VAV terminal and, where non-fan powered VAV terminal are used, there is no filter at the unit. All the routine maintenance (filter replacement, condensate pan cleaning) is centrally located at the air handling unit, minimizing maintenance needed within the occupied spaces. As the pressure increases in the main supply duct because the VAV boxes are closing their dampers https://1investing.in/ and are adjusting their dampers towards the minimum open setting, the air handler supply fan VFD slows down the fan. The opposite will happen due to the VAV boxes opening because of increased demand and the dampers are opening, in this case the VFD will cause the supply fan to speed up when the pressure in the main supply air duct drops. As the VAV boxes open or close due to demand called for by the temperature sensor in the space, the pressure in the main supply air duct will either increase or decrease.

In areas of the world where there are legally enforceable energy efficiency requirements for fan coils (such as the UK), DC Fan Coil Units are rapidly becoming the only choice. When I set the sub meter to measure the component performance, I found the heat pump loop is both heating and cooling the hotel instead of designed heating only, while the chilled water loop only cools the hotel during early morning. Since the heat pump cop (2.8) is lower than the chiller COP (5.1), the simulated results cannot reflect the design performance. In high-rise residential construction, typically each fan coil unit requires a rectangular through-penetration in the concrete slab on top of which it sits.

This adjustment is typically performed during the commissioning stage of building construction and remains fixed for the lifespan of the unit. Some zones are in cooling mode with their dampers at different percentages of being open, while other zones are in heating and one zone is off and receiving minimum air for ventilation. This is a very basic diagram of how zones may differ and why it’s important to consider how spaces are grouped vav vs fcu together, as each space may have a different solar exposure and cooling load profile. As the sun travels across the sky the zone dampers will open or close depending on their need for heating or cooling. Alternatively, certain manufacturers employ custom-wound Permanent Split Capacitor (PSC) motors with speed taps in the windings. These taps are set to the desired speed levels for the specific design of the fan coil unit.

When the temperature sensor in the space calls for cooling it sends a command to the VAV box controller which then adjust the supply air flow rate (CFM). The adjustment is done by an actuator rotating the VAV box inlet damper either open or closed in increments. Variable air volume is more energy efficient than constant volume flow because of the reduction in fan motor energy due to reducing fan speed (RPM) at partial load. As the cooling or heating demand is reduced because of a mild temperature day, the VAV Air Handler system can reduce the amount of air flow (CFM) by reducing the fan speed.

As a result, the office equipped with VAV consumes overall 4% more electricity than the office with FCU. Corner spaces are often difficult to include with other spaces because they have two exposures. Looking at the image we can see that there are two cooling zones between corner spaces that are on the south exposure that could be grouped into one zone, Zone #5 below. The same is true for the two zones between corner spaces on the North exposures, Zone #2. If you had interior zones they would be separated from any exterior zone because interior zones are often exclusively in cooling mode due to internal heat gains and the lack of heat loss from any exterior surfaces. This is the miniature of the air handling units.It is operated by the cooling water.

Find More

Categories

Follow Us

Feel free to follow us on social media for the latest news and more inspiration.

Related Content